Thermal mass flow meter Installation position and requirement for pipeline

Thermal mass flow meter Installation position and requirement for pipeline

 

1.The installation of instrument should be far away from the elbow, obstacles, reducer, valves, 

in order to assure a stable flow field, typically.Have a long straight pipe up and down, straight

long before more than 10 d, straight after long is greater than 5 d.

 thermal mass flowmeter.png

Often met in the figure below shows several ways of straight pipe required. 

  NO.   

   Pipeline  In front of the pipe section   

  The back pipe section  

   (1)

            straight pipe

  10 D 

                 5 D

   (2)

            bent pipe

   10 D  

                 5 D

   (3)

            flared tube

   15 D 

                 5 D

   (4)

      downstream of the valve

   20 D

                 5 D

   (5)

              shrink tube

   20 D

                 5 D

   (6)

            Under the pump

  30 D

                 5 D