Turbine flowmeter Wiring


Turbine flowmeter Wiring

 

 For technical parameter and connection terminal diagram pulse output per-amplifier, see Figure 8-1:

 

(1)Through thread M14*1, Type CMLWF-P-1 per-amplifier is screwed into installation thread holes on the 

body of the turbine flow meter, and then is locked with lock nuts.It is a kind of small-sized amplifier of 

low driving power, suitable for application in association with normal display instruments.

 

The output signals are delivered by the connector plugs through 3-wire shielded cable, with metal 

shielded network grounded. The connection is as per Figure 8-1.

a. Connection terminal diagram         

b. Connection Terminal Diagram for Connecting for Aviation Connector Plugs Terminals

 wiring.png


 Power supply source: VDD is the nominal value 12VDC

Output signal: square wave Low electrical level:≤1VDC

 

High electrical level:Power supply voltage VDD-3VDC

 

Output signal frequency: (at lower limit of flow) not lower than 20Hz

(2)Type CMLWF-P-2 pulse output per-amplifier is a amplifier featuring strong load capacity and adaptability 

of power supply source, and it may provide reliable pulse signals to PLC.

 

For wiring connection, please see Figure 8-1, in which +12VDC is modified to +24VDC.

 

Power supply source: VDD is the nominal value24VDC

 

Output signal: square wave

 

Low level:≤1VDC

High level:Power supply voltage VDD-3VDC

 

Output signal frequency: (at lower limit of flow) not lower than 20Hz

 

(3)Type CMLWF-P-3 pulse output preamplifier is a preamplifier designed for high temperature conditions of materials and structures of the detector parts on the basis of Type CMLWF-P-2 amplifier. Under the precondition that the ambient temperature is not higher than 55℃, the medium temperature may come up to 150℃.